How to change the display on an ATV212 drive to show 0-100% instead of 0-60hz range?

Issue:
How to change the display on an ATV212 drive to show 0-100% instead of 0-60hz range?

Product line:
Altivar 21, Altivar 212, ATV21, ATV212, S-Flex

Environment:
All models and all serial numbers.

Cause:
The drive originally is setup to output Hz on the main screen.

Resolution:
In order to display a percentage value instead of Hz, go into AUF, F--- submenu, and F702. Provide a value of 1.67 to convert 60 Hz to 100 percent.