Browse FAQs

What would cause a flashing C on the screen on an ATV21 / ATV212 drive?

Published date: 17 June 2019

Issue:
ATV21 / ATV212 drive has a flashing C on the screen and may not accelerate to full speed or shuts down with OLF or OCF displayed.

Product Line:
Altivar 21, Altivar 212.

Environment:
All models, All Serial numbers.

Cause:
Motor current in excess of the value set in F601.  Note:  If F701 is set to 1, then F601 setting is in Amperes.  If parameter F701 is set to 0 then F601 setting is in percentage of the drive rated output current as listed on the drive nameplate.  Factory default for F701 is 1, to indicate Amperes.

Resolution:
Ensure that F701 [Unit value selection (can be set to %, Amps, or Volts)] is set to desired setting, and:

F601 is set properly for the motor being used:
F601 should not be set higher than the motor Service Factor Amps.
If Service Factor Amps is not listed on the motor nameplate, multiply the Full Load Amps by the Service Factor as listed on the motor nameplate to obtain Service Factor Amps.  If the Service Factor is not listed on the motor nameplate, assume a service factor of 1.0 and set F601 to the Full Load Amps of the motor.

If these settings are correct, and current limit is still being reached, adjust the acceleration time (ACC) to a higher value. 

If Current limit is still being reached, investigate the incoming voltage to the drive:
Measure this with the motor stopped, then measure it again when a run command is given.  
If the incoming voltage is dropping significantly when the run command is given, then the motor will naturally pull more current.
Investigate the power quality coming in to the drive and correct as needed. 
If the incoming voltage is not dropping significantly,  investigate the mechanical properties of the installation.
Check for bad bearings or blockage or input dampers / valves that are not fully open. 
 
If the drive is programmed to match the motor name plate information correctly, the motor is sized properly for the load, and there are no problems with the incoming power quality, then this fault is an indication that your motor has to work harder than it should for this application.  Check for any mechanical reasons that would cause your motor to worker harder than it should need to.

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.