How to turn off the input phase loss in an ATV61 when using single phase?

Published date: 24 May 2018

Issue:
ATV61: How to disable input phase loss?

Product Line:
All

Environment:
All

Cause:
Supply voltage single phase

Resolution:
To disable Input phase loss
Under the Main Menu
Goto the Drive Menu enter
Goto the Fault Management Menu 1.8  enter
Goto the "Input Phase Loss" parameter enter 
Set "Input Phase Loss" to no (off) 
 