Technical FAQs

Ask a Question

Can the ATV312 be used to control speed of the motor with 0-10 milli amps?

Issue:
Where can you connect a mA signal to the ATV312 drive.

Product line:
Altivar ATV312 

Environment:
All models, all serial numbers 

Cause:
This drive uses terminals AI3 and COM for the mA signal.  It can be configured as 0-20mA or 4-20mA. 

Resolution:
Under the I-O_ menu go to CRL3 to adjust the minimum value and CRLH to adjust the maximum value. 
Was this helpful?
What can we do to improve the information ?