How is the ATV12 programmed to run via logic input on LI1 and adjust speed via dial?

Published date: 26 October 2018

Issue:   How is the ATV12 programmed to run via logic input on LI1 and adjust speed via dial?
 
Product Line:   ATV12
 
Environment:  All
 
Cause:   Terminal command with local reference
 
Resolution:   
Wire the run contact to +24 - LI1.
In the CtL menu, set Fr1 = AIV1, CHCF = SEP and Cd1 = tEr.
Press the dial twice to adjust speed as a percentage of the range LSP - HSP.


 