Does Schneider offer fingersafe covers for the 9422ATCF301?

Published date: 21 May 2019

Issue:
9422ATCF301 fingersafe covers are needed. 

Product Line:
Class 9422 Type ATCN, ATCF, TCN, TCF, ATDN, ATDF, TDF, TDN, ATEF, ATEN, TEN, TEF

Environment:
Flange or Cable operated Disconnect Switches only.

Resolution:
30-60A switches can use the cover SS06 and side skirt SS0306K.
100A switches can use the cover SS10 and side skirt SS10SK
****Note these covers do not work with the Bracket mounted disconnects or into existing Class 8538/8539 combination starters.   

See the attached details about these covers.