Can the Altivar 31 drive be set up to start with a jumpered run command or to restart without requiring the run command to be cycled?

Issue:
 
Can the Altivar 31 drive be set up to start with a jumpered run command or to restart without requiring the run command to be cycled?

Product Line:
ATV31
 
Environment:
2-wire control
 
Cause:
 n/a

Resolution:
Yes it can. If the drive is set for 2-wire control with the run forward command given on LI1, either by a closed contact or jumper wire on 24V-LI1, the drive can be set for level detection rather than the default transition detection.  In transition, the drive must detect LI1 transition from 0V to 24V for a run command.  Level detection will simply respond to the 24V on LI1 and will run.  In the IO menu, set tCC=2C and tCt=LEL.  The same logic will apply to the run reverse command.

 