Can Class T fuses be used with Altivar 31 drives? The manual only references Class CC or J.

Published date: 07 September 2018

The ATV31 units were tested with the Class J fuses however the 600V version of the Class T fuses have equivalent ratings. So can use the 600V Class T fuses but not the 300V Class T fuses.