What are the minimum required clearances for the ATS48 unit for enclosure mounting.

Published date: 19 July 2019

Issue:
What are the minimum clearances required on the ATS48 soft starters?

Product line:
Altistart 48, ATS48

Environment:
all

Cause:
Mounting inside an enclosure

Resolution:
There is a minimum of 4 inches (100 mm) on the top and bottom of the softstart.  A minimum clearance of 2 inches (50mm) on each sides.
The enclosure must also allow for proper ventilation to maintain a temperature of 40C (104F) and required wire bending space.