Can the ATV31 or ATV312 drives be used on a corner grounded or side grounded Delta system?

Issue:
Customer has a corner grounded or side grounded Delta Power system, wants to be sure the drive will work with it.

Product Line:
ATV312/ATV31
Altivar 312, Altivar 31

Environment:
All part numbers, all models

Cause:
n/a

Resolution:
Yes, the drives can operate on this type of power system.
However, it is necessary to disconnect the input RFI filter inside the drive.  
See the ATV31 or ATV312 installation bulletin, for directions on how to disconnect the input RFI filter.  
Give attention to the part numbers because not all ATV312/ATV31 drives have the RFI filter included.
If no RFI filter is built into the drive, it is not necessary to make any adjustments.

NOTE: Ungrounded systems may cause problems with high voltage with respect to ground. If the system floats high enough circuit boards can be damaged.

 