What is the recommended AC line fuse part number for ATV58HC25N4XZU?

Issue:   What is the recommended AC line fuse part number for ATV58HC25N4XZU?
 
Product Line:   ATV58
 
Environment:  ATV58HC25N4XZU
 
Cause:   Line fuse sizing
 
Resolution:   
For 350 HP Variable Torque loads the Bussman fuse part number is FWH-800A.
For 250 HP Constant Torque loads the Bussman fuse part number is FLW-600A.
These are not available through Schneider Electric / SquareD.
Use the Bussmann part numbers provided or an equivalent.


 