How does a user access the various parameter Levels for an ATS46 with the keypad?

Issue:
How does a user access the various parameter Levels for an ATS46 with the keypad?

Product Line:
ATS46

Environment:
All model numbers, all serial numbers.

Cause:
Customer couldn't get past level 1 when navigating the drive file.

Resolution:
On the back of the keypad you have two switches which are used to select the menu level you desire to get into.

Switch 1 is on the bottom and Switch 2 is on the top.  The ON position is to the left and is labeled as such.

Level 1: both switch 1 & 2 is in the ON postion -->
      -->This allows basic acceleration and deceleration control parameters.

Level 2: switch 1 is ON and switch 2 is off -->
      -->This includes level 1 parameters and additional set up of more advanced features.

Level 3: switch 1 is off and switch 2 is ON -->
      --> Reconfiguration of controller operation independent of level 1 & 2 parameters.


When the controller is Ready:
    * Controller may be started and stopped with presence of run command
    * Display of monitoring parameters (level 1 & 2 only)
    * Display and modification of configuration parameters
    * Display of fault codes
    * Prog LED lit

When Motor is Running:
    * Display of monitoring parameters
    * Display and modification of adjustment parameters
    * Display of configuration parameters; no modification of configuration parameters




CTA-ID : 2011219
Was this helpful?
What can we do to improve the information ?