What is the specifications on the 24v dc power supply and the total available mA for the ATV58 Econo Flex unit?

Issue:   What is the specifications on the 24v dc power supply and the total available mA for the ATV58 Econo Flex unit?
 
Product Line:   ATV58
 
Environment:  Econoflex drives
 
Cause:   24V power supply specs
 
Resolution:   
The 24v control supply specifications is Minimum 20 V; Maximum 30 V; I = 140 mA.

Total current of +24v internala supply is 140mA.  If more current is required, an external supply must be used.

Each LI on unit is rated for 10 mA.


 