How many faults does the Altivar 58 drive store in history?

Issue : 
How many faults does the Altivar 58 drive store in history?

Product Line :
Altivar 58
Flex58

Resolution : 
The drive stores the last 8 faults. There is no time or date stamp. The faults are stored in the order they occur (newest to oldest).
From the keypad only the last fault is available. (parameter LFt in the SUP menu)
To view previous faults use serial communications, Powersuite Software or the Message Display Center.

 