Configure PME web application to work over HTTP with a custom (non standard) port. Not able to login in PME web application (without SSL considerations)
Issue User is attempting to log in to PME 8.x web applications using the correct user name and password over HTTP with a custom port, but not able...
When using the REAL_TO_INT in Unity Pro, the rounding does not seem correct. 1.5 rounds to 2.0 and 2.5 also rounds to 2.0 instead of 3.0.
Goals and Symptoms To achieve proper rounding when converting REAL numbers to INT using Unity. Facts and Changes The ZEF file was created using Unity...
Can you please provide us the type 2 coordination table for starter with Class 20 LRD over load relay?
​There is no separate type 2 coordination available for starter with Class 20 LRD over load relay. But please refer the attached technical complementary...
What is the MTTF for the Tesys T Motor Management Relay?
We have the MTTF (Mean time to failure) value for this product. These values are provided by statistics regarding the experience of the product in...
I have installed Somove lite version 2.6 but not able to connect or create program of Tesys T or any of drive. How to solve the problem?
The DTM files for all Drives, Tesys T, Tesys U were part of Somove Lite software download until Somove Version 1.9.2.0. But the Somove version 2.0...
Can ATV312H***N4410 support pulse input reference? How can we set up the drive to accept pulse input as speed reference?
The specific version of drive having part reference like ATV312H***N4410 is designed  to support speed control with a pulse input reference of 24V...
Are the TeSys-T motor management relays comply with related EMC standards? Please provide necessary document?
Yes, the Tesys T comply to the various IEC/EN standards below related to electromagnetic interference. Please refer the attached characteristic pages...
Can we adjust the voltage output of an Altivar to be reduced from 380 to 220 Volts?
As per the understanding, the line supply voltage will be 380V or 400V, and you want to set the output voltage to the motor to be 220 V. Yes, It is...
What is the consumption of LC1D50** contactor with 220VDC coil control supply?
The inrush and sealed consumption is mentioned in the catalog and datasheets. The contactor LC1D50**** with DC control supply, the consumption given...
How the customer can test the Tesys GV2, GV3, GV7 MPCB thermal - magnetic tripping curve?
In general the thermal overload relay testing should be done as defined in IEC60947-2 standard.   Concerning thermal overload tripping level level...