When I enable the input range in my numeric display, it is set to min=0 and max=0 at runtime.

This issue occurs when you have a mismatch between the variable Data Type and the Numeric Display Data Type. For example, if your variable is INT and your Numeric Display is for "FLOAT", the input range will not work correctly. The data types must be the same. For INT use Integer. For REAL, use FLOAT.

 