Why does the Local/Remote button not work on the Process drive keypad?

Issue:
ATV630 drive, trying to switch into Local using the Local/Remote button, but that does not work.

Product line:
Altivar 600, ATV630, ATV650

Environment:
all

Cause:
Default programming

Resolution:
The factory settings for the Process drive is that the Local/Remote button is disabled.
To activate it, go to Complete Settings (CSt-) > Command and Reference (CrP) > HMI cmd. (bMP) and change it from Disabled (diS) to Bumpless (buMP).