What could cause Hex error 3410 (Network module missing) on an M580 L9_MSTR function block?

The high byte or MSB of the 4th implied word in the control array for the M580 L9_MSTR function block must be set to address 254 or 16#FE in order for the block to communicate out from the M580 native ethernet port.