What is the replacement for the Magelis XBTGT5330 HMI?

The Magelis XBTGT5330 HMI can be replaced by either the HMIGTO5310 or (HMIDT542 + HMIG3U). Here are details for the substitution replacements: 

Substitution of XBTGT5330 to HMIGTO5310: 
---VijeoDesigner applications are 100 % compatible 
---The cut-out is identical. 
---Screen resolution limited to VGA. 
---The communication ports are identical except on COM1 , no RS422-RS485 signal only RS232C For RS422-RS485 link , use a cables with converter like TSXPCX1030 for Schneider Twido/Premium PLC or XBTZ980+XBTZG919 for Mitsubishi FX PLC 
---Same certifications. 
---No support of SoMachine PLC functions 
---No extension Bus for Fieldbus modules ( Profibus , DeviceNet , CANopen ) 
---Only one USB port Host type A 
---No auxiliary interface for speaker or alarm output 
---Better Screen color TFT LED 65K , More Flash Memory , addition mini-USB Device port and use of SD card slot. 

OR 

Substitution of XBTGT5330 to HMIDT542 + HMIG3U 
---VijeoDesigner applications are 100 % compatible. 
---The cut-out is identical 
---Screen resolution SVGA. 
---The serial communication ports are identical but COM1 Subd9 RS422/R232C becomes the COM2 and the COM2 RJ45 RS485 becomes the COM1 
---Ethernet port with higher speed and with a second port 
---Same certifications. 
---Possible Extension Bus for Fieldbus modules ( Profibus , DeviceNet , CANopen ) 
---No support of SoMachine PLC functions 
---Same auxiliary interface for speaker or alarm output 
---Better Screen color TFT LED 16M and more resolution , More Flash Memory , addition mini-USB Device + Host/Device front USB ports and use of SD card slot. 