PME Web Application throws the error HTTP Error 500.24 - Internal Server Error An Asp.NET setting has been detected that does not apply in Integrated managed pipeline mode

Issue
While trying to access one or multiple tabs under Web Application, the following error is thrown

HTTP Error 500.24 - Internal Server Error
An Asp.NET setting has been detected that does not apply in Integrated managed pipeline mode






Product Line
PME 7.2, 7.2.2, 8.0

Environment
Web Application

Cause
ASP.Net impersonation is Enabled in the IIS that is hosting the Web Application of the PME.

Resolution
1. Open IIS manager
2. Select the server in the leftmost pane and double-click 'Authentication' under the IIS group in the middle tab.
3. Select ASP.Net impersonation and select 'Disable' at the top of the right pane.

 