Calibration issue with the PMESWT0100: impossible to launch

Goals and Symptoms
     Legal sealing switch is ON into the module : no way to launch the calibration the first time
Facts and Changes
M580, PMESWT0100
Causes and Fixes
      Set legal trade sealing to OFF, and transfer the configuration to the device