Technical FAQs

Ask a Question

Can the Modbus Plus tap assembly part# 990NAD23000 and the Modbus Plus part# AS-MBKT-xxx connectors be used on the same Modbus Plus network.

Yes.. The only thing to take notice of is that the Modbus Plus tap assembly part# 990NAD23000 module sets termination by jumper settings where as the AS-MBKT-185 connector has built in termination and the AS-MBKT-085 connector is non terminated for in-line connections..
Was this helpful?
What can we do to improve the information ?