Technical FAQs

Ask a Question

How can I prevent Undervoltage faults on ATV61 drives?

Drive nuisance trips on UVR, Undervoltage faults.

Product line:
ATV61, Altivar 61, ATV71, Altivar 71


Temporary voltage drops are causing UVR - Under voltage fault

Go to Drive Menu > 1.8 Fault Management > Undervoltage Mgt.  Change the Undervoltage timeout from 0.2s to somewhere between 5-10s. 

If the line voltage is less than 480VAC, we can also look at adjusting the Mains Voltage setting to 460V which lowers the trip level for the Undervoltage fault. 
Was this helpful?
What can we do to improve the information ?