BMXART0414 appears to be consuming one additional register.

Goals and Symptoms
BMXART0414 appears to be consuming one additional register.

Facts and Change
BMXART0414

Causes and Fixes
If you configure a BMXART0414 and an analog mdoule (e.g.,  BMXAMI0810) with no gap in the state ram assignment between the
two modules, the first registers of the analog will appear not to work or overwritten. 

The reason this occurs is because the BMXART0414 reserves one addtional register for the cold junction.

The workaround is to allocate a one register gap between the two modules.
 