How we can have diagnostic information for TMC2xxx additional cartridge analog I/O module within a TM221Cxxx PLC SoMachineBasic application program ?

Within TM221Cxxx /SoMachineBasic  we have  the possibility to add 1 or 2 optionnal cartridges ( depending on the TM221Cxxx PLC reference) 
Such cartridge  provides 2 analog inputs or outputs channels  as extension for the M221 PLC local I/Os.

For each channel it exists a dedicated system word object available for diagnostic .
It’s  %IWS.0.i   for an analog  input  channel
It’s %QWS.0.i  for an analog output channel
With i defined this way:
   i=100  for  the 1st channel of the cartridge located 1st slot
   i=101  for  the 2nd channel of the cartridge located  1st slot
   i=200  for  the 1st channel of the cartridge located 2nd  slot
   i=201  for  the 1nd channel of the cartridge located 2nd  slot

The definition of the code status/diagnostic value is as below:
For %IWS word content definition
0 Normal
1 Data conversion in progress
2 Initialization in progress
3 Input operation setting error or module without input
4 not used
5 High limit  reached
6 Low limit reached
7 Non-volatile memory error

For %QWS word content definition
0 Normal state
1 not used
2 Initialization in progress( after power on)
3 Output operation setting error or module without output
4 not used
5 not used
6 not used
7 Non-volatile memory error
 
 