Technical FAQs

Ask a Question

Bandwidth limitation on the service port of 140NOC78100

Goals and Symptoms
What is the limitation on the service port of a 140NOC78100?
Facts and Changes
Quantum, 140NOC78000
Causes and Fixes
According to the product spec, port 1 (service port) has ingress rate limiting as follows:
  • Unknown unicast, broadcast rate limit = 500 pps
  • Arp rate limit = 500 pps
  • Multicast rate limit = 30%
  • known unicast rate limit = 30%
Was this helpful?
What can we do to improve the information ?