Osisense XC - Tightening torque values of the XCMD mounting screws, not delivered with the limit switch

For the XCMD blue limit switches, such as for the XCSM red safety switches, the recommended tightening torque of the 2 mounting screws in the casing, are the following; provided for a maximum screw diameter of 4 mm (millimeter) or 0.157 in (inch) :
- minimum torque value : 1 N.m (Newton x meter) or 8.85 lb.in (pound x inch)
- maximum torque value : 1.5 N.m or 13.27 lb.in
Attached XCSM instruction sheet extract providing these values.
 