Technical FAQs

Ask a Question

How to program the ATV212 drive to follow the ACC and DEC set times?

Issue:
How is the ATV212 drive programmed to follow the ACC and DEC set times? 

Product Line:
Altivar 212

Environment:
ACC/DEC times

Cause:
N/A

Resolution:
Go into AUF (hit mode). 
Arrow down to AU1 and change value from 1 to 0.
 
Was this helpful?
What can we do to improve the information ?