Cannot change the HTTP or FTP password for the BMXNOE0110 using Web Designer.

Goals and Symptoms
Cannot change the HTTP or FTP password for the BMXNOE0110 using Web Designer.

Facts and Change
BMXNOE0110

Causes and Fixes
The selection for HTTP and FTP password on the target security window is greyed out and not selectable.



Due to cyber security reasons, the ability to change the HTTP and FTP passwords for BMXNOE0110 Factorycast
module using Web Designer is not allowed.   Changing of the passwords for the  BMXNOE0110 Factorycast module
must be performed from the 'Setup' web pages.