Why does the HMIG5U system restore program does not recognize the CFast card when using a card reader?

Issue:
Why does the HMIG5U system restore program does not recognize the CFast card when using a card reader?

Product Line:
HMIGTU, HMIG5U, CFast, recovery

Environment:


Cause:


Resolution:
The HMIG5U CFast cards are type 1.0 cards.  Some CFast card readers are type 2.0 and are not compatible with type 1.0.  To do a system restore, a type 1.0 CFast card read is needed.