Goals and Symptoms
Where is the M580 IP address located?
Facts and Changes
BMEP581020, BMEP582020, BMEP583020, BMEP584020, BMEP582040, BMEP583040, BMEP584040
Unity pro 10 and lower.
Causes and Fixes
The IP address is located in two system words: %SW6 and %SW7.
%SW6 contains the two last octets of the IP address and %SW7 contains the two first octets.