Technical FAQs

Ask a Question

M241/M251 Firmware update using Somachine Controller Assistant

Below are the instructions for M241/M251 Firmware Update using Somachine Controller Assistant:

Use a SD Card that has been Formatted Fat32
From SoMachine Central
Select Maintenance
Select Controller Assistant
Select Update Firmware..
Controller Type M241/M251
Select the Latest Firmware and the correct Controller
Select Next
Select Next
Select Write to..
Select Write
After it completes the Write.
Select Close
Eject the SD Card.
Power off the M251
Insert the SD card.
Power on M251
SD light should be flashing.
After about 3 minutes
SD Light should be on Solid.
Power off M251 and remove SD card.
Was this helpful?
What can we do to improve the information ?