Why do any changes made in Management Console take a while to update in the PME Web Applications?

Issue:
When changes are made in Management Console (New Devices, Device Renames, Changed Device Type, Logical Device changes, etc), a user has to wait in order to see these changes in PME Web Applications (Dashboards, Trends, Realtime Tables, AAV, Alarm Configuration and Hierarchy Manager). 

Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x

Environment:
Power Monitoring Expert Software Configuration

Cause:

In a normal working PME, the following rules apply to how data is "propagated" through the system:

  • Any change in Management Console (Device changes OR new Custom Measurement detection) will be applied to AppMods every 5 minutes (or when the AppMods services are restarted)
  • Any UI application that shows a list of Sources/Measurements (not counting Reporter) will cache their the list results for 15 minutes.
  • This implies a worst case delay of 20 minutes (15+5) before you see your changes in PME. 
  • The steps below simply short circuit the logic to instantly have AppMods updated and all application cache values purged.

Resolution:

Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

 1. In SQL Management Studio, run the following script (this is a safe script to run):

USE [ApplicationModules]
-- This script will clear the ApplicationModules provider cache.  It is
-- safe to run as often as you like! 
DELETE FROM [ApplicationModules].DataStore.TicketResultReference
DELETE FROM [ApplicationModules].DataStore.TicketResult
GO

 2. Restart service "ApplicationHost CoreServices"

 3. Wait 10 seconds, then refresh the PME Web application in the browser that you want updated.