Issue
With the release of the PM8000 and the PM5000 there is an entirely new method of adding devices. Previously daisy chained devices had a master and each device downstream from that would be a slave, however with Ethernet daisy chaining this structure no longer applies.

Product Line
ION Enterprise 6.0
PME 7.2, 7.2.2, 7.2.3
PME 8.0, 8.1
PM5560
PM5563
PM8000

Environment 
Meter Initialization 

Resolution 
When adding Ethernet daisy chained PM8000 or PM5000 meter into the Management Console PME or ION Setup (The IP address has to be unique for all the PM5000 or PM8000, although the Gateaway and Subnet mask address is shared), the Ethernet Device option needs to be selected in Management console (No site is added in Management Console, and when adding the site in ION Setup, select Ethernet and leave Gateway unchecked)

Note: Only the PM5560 and PM5563 have dual Ethernet ports. All other meters within the PM5000 series will either be added as an Ethernet device or serially connected device. 