How can I make sure that my Magelis HMISCU starts in Run mode after a power cycle?

1) Make sure the "Start All applications after a download or online changes" is selected



2) Create a Vijeo Designer action to write a non-zero value to @prop:0 on startup.

2.1) Create a new external variable INT in Vijeo Designer and address it as @prop:0.


2.2) Create an action to write a non-zero value to the variable on startup.