Unity Pro V10.0 - Issue using IEC_BMDI_M function block

Goals and Symptoms  

Do not use IEC_BMDI_M as it's not running as expected with side effect.

Facts and Changes

This EF is provided in Unity Pro V10.0.
The length input parameter is not properly respected while doing bit to word copy.
If lenght is adjusted to 16, to copy 16 bits to 1 word, we have 16 first bits copied but not only.
It's continued doing copy up to 256bits, mean 16 words in output are writen by this EF in all cases.

Causes and Fixes

A Unity V10 Hot fix will be provided.
Delivery date and hotfix name to be confirmed.

 