Selecting Micrologic Device Type in Management Console

Issue
Incorrect selection of Micrologic device type can lead to lag communication and manual configuration of Vista default device diagrams.

Product Line
Software: ION Enterprise, Structureware Power Monitoring, Power Monitoring Expert
Circuit Breakers: Masterpact, Powerpact, Compact NS, Compact NSX

Environment
Applications with breaker communication with Schneider Electric power monitoring software

Cause
Need to select the correct device type for Micrologic circuit breaker

Resolution
The below tables display the correct device type for a given Micrologic trip unit type.
Trip Units PME Device Type
Micrologic 2.0 No Communications
Micrologic 3.0 No Communications
Micrologic 5.0 No Communications
Micrologic 2.0 Ammeter Micrologic A or Micrologic A IFE_IFM
Micrologic 3.0 Ammeter Micrologic A or Micrologic A IFE_IFM
Micrologic 5.0 Ammeter Micrologic A or Micrologic A IFE_IFM
Micrologic 6.0 Ammeter Micrologic A or Micrologic A IFE_IFM
Micrologic 7.0 Ammeter Micrologic A or Micrologic A IFE_IFM
Micrologic 2.0 Energy Micrologic E or Micrologic E IFE_IFM
Micrologic 3.0 Energy Micrologic E or Micrologic E IFE_IFM
Micrologic 5.0 Enegry Micrologic E or Micrologic E IFE_IFM
Micrologic 6.0 Energy Micrologic E or Micrologic E IFE_IFM
Micrologic 5.0 Power Micrologic P or Micrologic P IFE_IFM
Micrologic 6.0 Power Micrologic P or Micrologic P IFE_IFM
Micrologic 7.0 Power Micrologic P or Micrologic P IFE_IFM
Micrologic 5.0 Harmonic Micrologic H or Micrologic H IFE_IFM
Micrologic 6.0 Harmonic Micrologic H or Micrologic H IFE_IFM
Micrologic 7.0 Harmonic Micrologic H or Micrologic H IFE_IFM
 
Trip Units PME Device Type
Micrologic 2.2 No Communications
Micrologic 2.3 No Communications
Micrologic 3.2 No Communications
Micrologic 3.3 No Communications
Micrologic 5.2 Ammeter Micrologic A Compact NSX
Micrologic 6.2 Ammeter Micrologic A Compact NSX
Micrologic 5.3 Ammeter Micrologic A Compact NSX
Micrologic 6.3 Ammeter Micrologic A Compact NSX
Micrologic 5.2 Energy Micrologic E Compact NSX
Micrologic 6.2 Energy Micrologic E Compact NSX
Micrologic 5.3 Energy Micrologic E Compact NSX
Micrologic 6.3 Energy Micrologic E Compact NSX