It is possible to detect a USB memory stick and the volume name on an LMC078?

There is no direct function or variable showing that a USB key is available or not and the related root path.  But you can use the following workaround:
 
    depending on the status value you know
      0  : USB key is mounted and the device has no partition table   --> You must use ´usb2msd:0/' for the root path of the USB memory stick
     -1  : USB key is mounted but the device has a partition table      --> You must use ´usb2msd:1/' for the root path of the USB memory stick
   -318 : USB key not mounted
 