Can my SCADA system communicate to other Modbus Plus devices through the M340 Modbus Plus Proxy?

The M340 Modbus Plus proxy is only used to communicate to the M340. In order for a SCADA system or another device to communicate out to other Modbus Plus devices, a gateway would need to be used. 
The Niobrara MEB II is the recommended gateway at this time. 