Technical FAQs

Ask a Question

Modbus devices connected to EtherGate gateway show 65535 or 0 in ION Setup

Issue

A Modbus device is connected to ION Setup through an EtherGate gateway connection. Communications are established, but the meter menus are only displaying "65535" or "0" values, which correspond to an empty Modbus register.


Communications are established with the Modbus meter


Values in ION Setup menus display either 65535 or 0


Serial settings of gateway are set to EtherGate protocol

Product Line

  • Ethergate ION meters
  • Modbus meters

Environment

ION Setup v3.0

Cause

The IP port for the gateway is incorrectly set to 502. An Ethergate connection communicates through IP ports 780X, where X corresponds to the appropriate com port of the gateway.

IP Port of EtherGate gateway set to 502

Resolution

Set the IP Port of the gateway to 780X, where X is the EtherGate com port.

Port changed to 7802, which corresponds to the EtherGate over Com 2


ION Setup menu displays meaningful values

 
Was this helpful?
What can we do to improve the information ?