Why can I not see the ethernet web page on and ATV61 or ATV71 drives?

Issue:
Why can I not see the ethernet web page on and ATV61 or ATV71 drives?.

Product Line:
Altivar 61 and 71 drives

Environment:
All models and serial numbers with Ethernet IP option card VW3A3316

Cause:
The Java 1.8 is not supported at this time.

Resolution:
Roll back the Java version to 1.7.67  See the document attached.