Cannot View diagrams in engineering client after running EPSS Generator tool

Diagrams created from EPSS generator tool will not open in engineering client , Diagrams open fine in Vista on from the server.

Product Line
PMEHC 7.22
PMEDC 7.22

StruxureWare Power Monitoring Expert Vista Application

EPSS Generator tool does not bring the network  path over for the diagrams.  Right clicking on the link in vista will show the local server path for the diagrams "C:\Programfiles\Schneider-electric\powermonitoringexpert\\diagrams\ud\EPSS\diagram.dmg


1. In Vista engineering client click "File > Open" you will see the server path to the diagrams you can copy this or note it.

2. Right click open on the link in the engineering client and select the action tab in the path field.

3. Remove the local path keeping the diagram name and past the server path you copied,  it will now look something like this:

4. You will need to do this for each link created by the generator tool.