Cannot View diagrams in engineering client after running EPSS Generator tool

Issue
Diagrams created from EPSS generator tool will not open in engineering client , Diagrams open fine in Vista on from the server.

Product Line
PMEHC 7.22
PMEDC 7.22

Environment
StruxureWare Power Monitoring Expert Vista Application

Cause 
EPSS Generator tool does not bring the network  path over for the diagrams.  Right clicking on the link in vista will show the local server path for the diagrams "C:\Programfiles\Schneider-electric\powermonitoringexpert\\diagrams\ud\EPSS\diagram.dmg

Resolution

1. In Vista engineering client click "File > Open" you will see the server path to the diagrams you can copy this or note it.

2. Right click open on the link in the engineering client and select the action tab in the path field.

3. Remove the local path keeping the diagram name and past the server path you copied,  it will now look something like this:
        \\Powerlogic02\ION-Ent\config\diagrams\ud\EPSS\diagram.dgm

4. You will need to do this for each link created by the generator tool.
Was this helpful?