Advantys web page returns "600 error access builtin CGI File"

Goals and Symptoms
Advantys web page returns "600 error access builtin CGI File"

Facts and Change
All Advantys STBNIPxxxx Ethernet modules

Causes and Fixes
Opening a web page for the Advantys Ethernet module returns the error 'Advantys web page returns "600 error access builtin CGI File"'.

This occurs because the Java Runtime Environment is not installed on the PC.  To resolve the issue, a minimum Java Runtime version of 6.45 must be installed.
If you install Java Runtime version 7 or above, you will need to addd an exclusion for the IP address in the Java Security settings.

To make an exclusion in the security settings:
  • Open the Control Panel.
  • Double click on Java
User-added image
 
  • Click on 'Security'.
  • Click on 'Edit Site List'.
User-added image
 
  • Add the IP address of the Advantys NIP (e.g., http://192.168.1.44)
  • Click on OK.
User-added image
 