Why do I get the Error "Application has halted due to: Unhandled, java/lang/NullPointerException IVM: except.c: line 322" on the XBTGT7340?

The NullPointerException errors are usually associated with the SRAM data being corrupted. A couple of ways of clearing this corrupted SRAM data is to do a download via ethernet or USB cable (XBTZG935) and check off the "Delete All Runtime Data" box.