Video: How do you put the ATV12 drive in local mode to run off the face of the drive?

Issue:
How do you put the ATV12 drive in local mode to run off the face of the drive?

Product Line:
Altivar ATV12

Environment:
All

Cause:
Requirement to operate the ATV12 in local mode using the wheel for speed control and the start stop buttons for starting and stopping.

Resolution:

Programming:
  • Hold the MOD button for 3 to 4 seconds to put this drive in local mode.
  • You will see LOC displayed followed by rdY.
  • While in Local Mode, 3 LEDs will flash top to bottom on the left side of the display to indicate Local Mode is enabled.
  • If you need to go back to remote mode hold the MOD button again for 3 to 5 seconds.
Please note: If you go between local and remote modes you will reset your logic inputs and CTL FR1 parameters to factory default.