What hierarchies does the Branch Circuit Reports in Power Monitoring Expert for Data Center (PME4DC) support?

One of the prerequisites for running the Branch Circuit Add-On Reports in PME4DC is to have the correct hierarchy successfully loaded and configured.

Product Line:
Power Monitoring Expert for Data Center 7.2.x

Power Monitoring Expert for Data Center Software Configuration

The Branch Circuit Power Report and the Branch Circuit Energy Report only supports specific hierarchies. When an unsupported hierarchy template is installed, the reports will not render any data.

It only supports the 2 hierarchies that are shipped with PME4DC  i.e. either the 2 level customer/circuit or 3 level customer/rack/circuit. These templates are located in the ...\Power Monitoring Expert DC Ed\Applications\HierarchyManager\SampleTemplates\DataCenter folder. It will not support any other hierarchy templates.