Applying changes to the Unitelway driver returns 'Can't reset driver' error.

Goals and Symptoms
Applying changes to the Unitelway driver returns 'Can't reset driver' error.

Facts and Change
Unity

Causes and Fixes
If you try to apply the changes made to the Unitelway driver and the NA_Service is not running on the PC,
the error 'Can't reset driver' will get returned.
User-added image

User-added image

To resolve the issue, log into the PC as an administrator and start the NA_Service:
  • Open a windows folder.
  • Right click on 'Computer'.
  • Select 'Manage'.
User-added image
  • Click on 'Services and Applications'.
  • Click on 'Services'.
User-added image
  • Scroll down to find 'NetAccess Service'.
User-added image
  • Right click on 'NetAccess Service and select Start.
  • The 'Startup Type' should be defined as 'Automatic'.
User-added image

If the 'Startup Type' is not defined as 'Automatic'.  This is an indication that the user did not have
full adminstrator rights when Unity and the driver was installed or something else (i.e., anti-virus
software, anti-spyware software, etc.) running on the PC prevented the changes to the registry..

To change the 'Startup Type':
  • Right click on 'NetAccess Service' and select 'Properties'.
User-added image
  • Click on the dropdown arrow next to 'Startup Type'.
  • Select 'Automatic'
User-added image
  • Click on 'Apply'.
  • Click on 'OK'.
User-added image
  • Close the 'Computer Management' window.


 