Technical FAQs

Ask a Question

Why are I getting an error: "The Main Drive or Secondary Drive is full. Runtime cannot execute" on the Magelis when downloading with a USB stick?

Issue:
Why are I getting an error: "The Main Drive or Secondary Drive is full.  Runtime cannot execute" on the Magelis when downloading with a USB stick?

Product Line:
XBTGC/GH/GK/GT, HMIGTO/STO/STU

Environment:


Cause:


Resolution:
This error message could be due to the Magelis may not have a CF card/SD card installed.  To confirm goto the Data Locations in Vijeo Designer and if you have "User Application", "Data Files / Forms", "Recipes", or "Web Server" set for Secondary Drive.  Then that means that you need to have a CF/SD card (depending on unit) installed in the unit.  Once you add a CF/SD card, reloading from the USB stick complete successfully.
Was this helpful?
What can we do to improve the information ?