Can the Adapter Plate that is used to replace the ATV58 with the ATV61/71 be used when converting the Flex58 to the ATV61/71?

Issue:
Can the Adapter Plate that is used to replace the ATV58 with the ATV61/71 be used when converting the Flex58 to the ATV61/71?
 
Product Line:
ATV61 and ATV71  

Environment: 
Frame size 2 to frame size 8

Cause:
Converting from the ATV58/FLEX58 to the ATV61/71

Resolution:
The Adapter plate that is used for mounting the ATV61/ATV71 in the same foot print as the ATV58 cannot be used to replace the FLEX58 with the ATV61/71 . The foot print of the FLEX58 is different from that of the ATV58, this difference is not compatible with the mounting plate.