Technical FAQs

Ask a Question

Video: How can you program the ATV212 drive to run in local mode (face of the drive)?

Issue:
How can you program the ATV212 drive to run from in local mode (face of the drive)?

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Needs to use the run/ stop buttons on the face of the drive.

Resolution:
Programming as follows:
Push Mod until you see AUF
Once at AUF arrow down to CNOD and set to 1 ( local mode) enter
arrow up to FNOD and set to 3 ( local knob for speed)

See that attached programming manual and video for assistance on setting up the reset of the drives programming settings.
 
Was this helpful?
What can we do to improve the information ?